Bypass input and output overcurrent protection and bypass, output and accessory disconnect switchesmust be provided by the user.44..55 UUnnppaacckk aanndd uunnllooaadd tthhee UUPPSSBefore you start to unpack and unload the UPS, look at the TipNTell indicator on the package surface.When you have unpacked and unloaded the UPS, look at the DropNTell indicator on the back of the UPS.If the equipment has been correctly transported in the upright position, the indicators should be intact. Ifthe TipNTell indicator arrow has turned all blue or the arrow head(s) of the DropNTell are black, contactthe appropriate parties to report inappropriate transportation.WARNINGThe UPS cabinet is heavy. If you do not obey the unpacking instructions, thecabinet may tip over and cause serious injury.Do not tilt the UPS cabinet more than 10 degrees from the vertical or the cabinetmay tip over.For transportation purposes, the UPS cabinet is bolted onto a wooden pallet. To remove the pallet, do thefollowing:1. Before you unload the cabinet from the pallet, use a forklift or other material handling equipment tomove the cabinet to the installation area. Insert the forks of the forklift between the skids on the bottomof the unit.2. Make a visual inspection and examine that there are no signs of shipping damages. Examine theTipNTell and refer to the instructions next to the indicator on the package. The DropNTell indicator islocated on the rear panel of the UPS and can be verified after the next step.EATON 91PS/93PS UPS USER’S AND INSTALLATIONGUIDEP-164000672 - 005 2023 www.eaton.eu 3388