8. Remove the shipping brackets.NOTE: After you have removed the shipping brackets, move the unit immediately away from the pallet.After you have removed the shipping brackets and retracted the leveling feet, donot use a forklift to move the unit while it is still on the pallet. Note that the UPScabinet is heavy and there are casters under the cabinet.9. Slowly roll the cabinet toward the ramp edge. Be careful not to push the cabinet too much or too fastsince it may cause the cabinet to tip over. Note that the cabinet is heavy. Make sure that you haveenough manpower to handle and support the unit while rolling it off the pallet.10. Roll the cabinet to its final installation location.11. To secure the UPS cabinet in position, lower the leveling feet until the cabinet is not resting on thecasters and the cabinet is level. With 91PS/93PS 8-10 kW UPS, reattach the shipping brackets to theUPS cabinet to provide extra support. There are 2 options for positioning the shipping brackets: onboth sides of the unit or on the front and rear of the unit.NOTE: If you remove the cabinet from its original installation location and transfer it to a new location on apallet, lower the leveling feet until the cabinet is not resting on the casters. In addition, attach the shippingbrackets to the cabinet and the pallet.EATON 91PS/93PS UPS USER’S AND INSTALLATIONGUIDEP-164000672 - 005 2023 www.eaton.eu 4400