Technical DataMVX9000 User Manual A-5Technical DataTable A-3: MVX9000 460V SpecificationsVoltage Class 460V SeriesModel Number MVX_ _ _AO-4 001 002 003 005 007 010Max. Applicable Motor Output (kW) 0.75 1.5 2.2 3.7 5.5 7.5Max. Applicable Motor Output (hp) 1 2 3 5 7-1/2 10Output Rating Rated Output Capacity(kVA) 2.3 3.1 3.8 6.2 9.9 13.7Rated Output Current (A) 3 4 5 8.2 13 18Max. Output Voltage (V) Proportional to input voltageRated Frequency (Hz) 0.1 to 400 HzInput Rating Rated Voltage 342 to 528V ACFrequency Tolerance 50/60 Hz ± 5%3-phase Rated InputCurrent 4.2 5.7 6 8.5 14 23ControlCharacteristics Control System SPWM (Sinusoidal Pulse Width Modulation)Output FrequencyResolution 0.1HzOverload Endurance 150% of rated current for 1 minuteAcceleration/DecelerationTime 0.01 to 600.00 secondsTorque Characteristics Including the auto-torque, auto-slip compensation; startingtorque can be 150% at 1 Hz in vector, 3 Hz in V/FV/F Pattern Adjustable V/F pattern or sensorless vectorStall Prevention Level Set to percentage of rated currentOperatingCharacteristics FrequencySetting Keypad Set by UP, DOWN keys or potentiometerExternalSignal Potentiometer-5 kW/0.5W, 0 to +10V DC or 0 to +5V (Inputimpedance 47 kW), RS-485 interface, 4 to 20 mA (Inputimpedance 250W), 1 to 7 step speeds, PID feedbackOperationSettingSignalKeypad Set by START, STOP, RIGHT and LEFT keysExternalSignal FWD/STOP, REV/STOP (RUN/STOP, FWD/REV), 3-wire control,serial communicationDigital Input Signal Multi-step selections 1 to 7, Jog, acceleration/decelerationinhibit, first/second acceleration/deceleration switch, counter,External BB (Pause), PLC operation. Terminals have 5Vpotential and must be brought to DC common to enable(Sinking).Digital Output Indication Operating, Up to frequency, Desired frequency, Non-zero B.B.,Abnormal indication, Local/Remote indication, PLC, LowVoltage.Analog Output Signal Analog frequency/current signal output.