MVX9000 Parameter ListingB-10 MVX9000 User ManualParameter TablesTable B-5: 60 — MOTOR CONTROLModbus Groups Page # Description Range Default UserSettings0400H 60.01 5-50 Motor Rated Current 30 to 120% FLA0401H 60.02 5-50 Motor No-LoadCurrent 00 to 99% 0.4*FLA0402H 60.03 5-50 Motor Auto Tuning 00: Disable 0001: DC test02: DC test and no load test0403H 60.04 5-50 Motor’s StatorResistance(calculated via autotune or enteredmanually)00 to 65535 m Ohms 000404H 60.05 5-51 DC Braking CurrentLevel 00 to 100% 000405H 60.06 5-51 DC Braking Timeupon Start-up 0.0 to 5.0 sec 0.00406H 60.07 5-51 DC Braking Timeupon Stopping 0.0 to 25.0 sec 0.00407H 60.08 5-52 Frequency-point forDC Braking 0.0 to 60.0 Hz 0.00408H 60.09 5-52 TorqueCompensation 00 to 10 000409H 60.10 5-53 Slip Compensation 0.00 to 10.00 0.0040AH 60.11 5-53 PWM CarrierFrequency 115V/230V/460V: 1 to 15 KHz 9575V: 1 to 10 KHz 6