Group 30 — Inputs5-10 MVX9000 User ManualDescriptions ofParameter SettingsExample 2:This example shows a 10 Hz positive offset with full use of the 0 – 10V analoginput or potentiometer scale. A 0V input = 10 Hz and 10V input = maximumoutput frequency.Calculation of Potentiometer Slope30.09=(1-30.07) x 100% = 83.3%Figure 5-7: 10 Hz Positive OffsetDefaults:20.07=60Hz Maximum Output Frequency30.07=16.7% (10hz/60hz) x 100=Potentiometer Offset30.08=0 Bias polarity30.09=83.3% Potentiometer Slope30.10=0 Potentiometer DirectionHz0V 10V350 60Potentiometer ScaleMax.OutputFreq.Bias Adjustment(20.07)60 Hz10V20 mA5V12 mA0V4 mA0 Hz10 Hz