External Wiring3-6 MVX9000 User ManualStorage andInstallationExternal WiringFigure 3-3: External WiringMotorLoadReactorPower SupplyFuseMagneticContactorLine ReactorEMI FilterL1 L2 L3LINEMOTORT1 T2 T3B1B2BrakingResistorTable 3-1: Wiring ItemsNote: Please refer to Appendix C formore details on the Circuit Breaker andFuse Specification tables.Items ExplanationsInputPowerPlease follow the specificpower supply requirementshown in Appendix A.Fuse Please check the FuseSpecification table inAppendix C for proper fuseselection.MagneticContactor(Optional)Please do not use a MagneticContactor as the ON/OFFswitch of the AC drive, thiswill reduce the operating lifeof the AC drive. Thecontactor should only beused as a safety device fordisconnecting power to thedrive.Line/LoadReactor(Optional)To improve the power factor.An AC Reactor may benecessary when capacity isabove 1000 kVA, and thewiring distance is within 10m.EMI Filter(Optional)Used to reduce theelectromagneticinterference.BrakingResistor(Optional)Used to reduce stoppingtime of the motor. Pleaserefer to the Breaking Resistortable in Appendix C forspecific Braking Resistors.