MVX9000 Parameter ListingB-4 MVX9000 User ManualParameter TablesTable B-2: 30 — INPUTS (Continued)Modbus Groups Page # Description Range Default UserSettings010BH010CH010DH010EH30.1230.1330.1430.155-155-155-165-16Digital Input Terminal(DI3)Digital Input Terminal(DI4)Digital Input Terminal(DI5)Digital Input Terminal(DI6)17: Acceleration/Decelerationl Prohibit 0506070318: Run Enable19: Base Block (NO)20: Base Block (NC)21: PID Disable22: Run PLC Program23: Pause PLC Program24: Counter Trigger signal25: Counter Reset26: First/second Source ofMaster Frequency27: Increase speed duringRUN or STOP state28: Decrease speed duringRUN or STOP state29: Output Shut Off (NO)30: Output Shut Off (NC)31: Auto Location – Operation& Frequency by First source(P50.01 & P50.02)32: Hand Location –Operation & Frequency bySecond source (P50.57 &P50.60)33: LOC – Operation &Frequency by Second source(P50.57 & P50.60)010FH 30.16 5-25 Final Count Value 00 to 9999 000110H 30.17 5-25 Intermediate CountValue 00 to 9999 000111H 30.18 5-25 1st Preset Speed 0.0 to 400.0 Hz (100.0%) 0.00112H 30.19 5-25 2nd Preset Speed 0.0 to 400.0 Hz (100.0%) 0.00113H 30.20 5-25 3rd Preset Speed 0.0 to 400.0 Hz (100.0%) 0.00114H 30.21 5-25 4th Preset Speed 0.0 to 400.0 Hz (100.0%) 0.00115H 30.22 5-26 5th Preset Speed 0.0 to 400.0 Hz (100.0%) 0.00116H 30.23 5-26 6th Preset Speed 0.0 to 400.0 Hz (100.0%) 0.00117H 30.24 5-26 7th Preset Speed 0.0 to 400.0 Hz (100.0%) 0.00118H 30.25 5-26 Display Hz or % 00: Frequency (Hz) 0001: Percentage (%)02: User Definition by 0.000 –max. unit0119H 30.26 5-26 Extension Input DI7 same 30.12 to 30.15 00011AH 30.27 5-26 Extension Input DI8 same 30.12 to 30.15 00011BH 30.28 5-26 User DefinitionDisplay FrequencyMax Unit0.000 – 1.000 1.000