2 Engineering2.5 Compatible variable frequency drive16 DX-NET-SWD... 08/14 MN04012009Z-EN www.eaton.com2.4.4 SWD-AssistThe SWD-Assist program provides valuable support in the engineering ofyour SmartWire-DT topology. SWD-Assist is software that runs underoperating systems Windows 2000 (SP 4), Windows XP, Windows Vista(32-bit) or Windows 7 and relieves you of the planning work required for anSWD topology.The DX-NET-SWD… SmartWire-DT interface module can be used inSWD-Assist version V 1.80 and higher.2.5 Compatible variable frequency drive• The DX-NET-SWD1 SmartWire-DT interface module can be used with allDA1 variable frequency drives with an IP20 or IP55 degree of protection• The DX-NET-SWD3 SmartWire-DT interface module can be used with allDC1 variable frequency drives and DE1 variable speed starters with anIP20 degree of protection.2.6 Exchange of variable frequency drivesIf you replace a DA1 or DC1 variable frequency drive or a DE1 variable speedstarter in a supply system, you do not need to press the configuration buttonafter replacing it and switching on the voltage!The configuration button only needs to be pressed if you replace theinterface module. Doing so will assign a new network address to themodule.→ The SWD-Assist program can be downloaded for free on theInternet at: http://downloadcenter.moeller.net DANGERBefore replacing a DA1 or DC1 variable frequency drive or aDE1 variable speed starter, make sure to switch off the voltageand the entire SmartWire-DT system!NOTICEWhen replacing a DA1 or DC1 variable frequency drive or aDE1 variable speed starter, the order of the SmartWire-DTmodules must not be altered.