4 Commissioning4.5 Acyclic data60 DX-NET-SWD... 08/14 MN04012009Z-EN www.eaton.com5 1 3 1 ✓ – – STOP ro Rel motor output5 2 0 0 P0-26 – – STOP ro kWh meter kWh counter, total sinceinitial commissioning1 P0-26 – – STOP ro kWh counterR kWh counter; the value canbe reset2 P0-27 – – STOP ro MWh counter MWh counter, total sinceinitial commissioning3 P0-27 – – STOP ro MWh counterR MWh counter, value can bereset550 0 P0-03 – P00-04 STOP ro Int8 DI1 Status Digital input states1 ✓ – ✓ STOP ro Int8 DI2 Status2 ✓ – ✓ STOP ro Int8 DI3 Status3 ✓ – ✓ STOP ro Int8 DI4 Status4 ✓ – – STOP ro Int8 DI5 Status5 ✓ – – STOP ro Int8 DI6 Status6 ✓ – – STOP ro Int8 DI7 Status7 ✓ – – STOP ro Int8 DI8 Status560 0 P0-01 P00-01 P00-01 - ro Analog input1 Magnitude of signal atanalog input 1, taking scalingand offset into account1 P0-02 P0-02 – STOP ro Analog input2 500 ≙ 50.0%570 0 ✓ – – STOP ro Analog output1 500 ≙ 50.0%1 ✓ – – STOP ro Analog output2 500 ≙ 50.0%615 2 P5-14 – – STOP rw NETInputPZD3 Input process data for fieldbus modeFor more information, pleaserefer to the manual for thebasic device.3 P5-13 – – STOP rw NETInputPZD4 Input process data for fieldbus modeFor more information, pleaserefer to the manual for thebasic device.616 2 P5-12 – – STOP rw NETOutPZD3 Output process data for fieldbus modeFor more information, pleaserefer to the manual for thebasic device.3 P5-08 – – STOP rw NETOutPZD4 Output process data for fieldbus modeFor more information, pleaserefer to the manual for thebasic device.PNUIndexPNUSubindexParameter number inspecific deviceAccess right Data type Name DescriptionDA1 DC1 DE1 RUN/STOPro/rw