4 Commissioning4.4 Cyclic data36 DX-NET-SWD... 08/14 MN04012009Z-EN www.eaton.com4.4.2 Simplified starting with profile 24.4.2.1 DOL starting in profile 2Use the following settings (as hexadecimal values) for the command (outputbytes 0 and 1):Table 7: StartingTable 8: Stop with rampTable 9: Stop, with run-downTable 10: Fault scenarioSetpoints set using output bytes 2 and 3 will be represented as integervalues. 100% equals 4000hex .The operating direction is specified with a negative setpoint:For example: -100% ≙ C000 hexActual values will be returned in the same format using input bytes 3 and 4.Value description16#0000 Voltage on device and connection present.16#047E This command changes the drive to Ready, but it is still at a standstill.16#047F This changes it from Ready to RUN and it starts to move if a setpointvalue is set.Value description16#047F Running in operation.16#046F Performs the ramp stop.16#047F This will cancel the ramp stop, and the variable frequency drive/variable speed starter will keep running.Value description16#047F Running in operation.16#047E Performs the uncontrolled stop.16#047F This will cancel the ramp stop, and the variable frequency drive/variable speed starter will keep running.Value description16#047F A fault occurs during ongoing operation.16#0507 Resets the variable frequency drive/variable speed starter16#047F Start after troubleshooting