4 Commissioning4.4 Cyclic data40 DX-NET-SWD... 08/14 MN04012009Z-EN www.eaton.com4.4.5 Profile 1 (8 bit): Outputs (control)Output bytes 0 and 1 (Short) are mapped as follows on SmartWire-DT.Table 12: Profile 1: Output bytes 0 and 1Byte 1 is only needed for internal, SWD-specific functions.Byte: BIT Designation Meaning0 0 FWD Start ReverseA value of 1 will start the variable frequency drive/variable speed starterin the clockwise operating direction.1 REV Start anticlockwise operationA value of 1 will start the variable frequency drive/variable speed starterin the anticlockwise operating direction.2 EN_Op Enable operation0: Stop (immediate disconnection of the output)1: OperationIf this bit has a value of 0, the variable frequency drive's/variable speedstarter's output will be switched off directly. To start the device, this bitmust be set to a value of 1 and the FWD or REV bit must be set to 1 as well.3 FaultAck Fault Acknowledge0: Do not acknowledge current fault1: Acknowledge current fault (rising edge: 0 → 1)This bit can be used to reset a fault in the variable frequency drive/variablespeed starter. The fault acknowledge function will only respond to a risingedge, i.e., to the value changing from 0 to 1.4 I1 programmable input 1Can be used to set one of four binary-coded fixed frequencies.→ Table in I25 I2 programmable input 2Can be used to set one of four binary-coded fixed frequencies.6 I3 programmable input 3Can be used to switch the setpoint input from a fixed frequency to ananalog input.0: Setpoint provided with fixed frequency1: Setpoint provided with analog input7 I4 programmable input 4Reserved – not used as of this writing1 0 - 7 – Reserved – not used as of this writingI1 I2 Fixedfrequency0 0 FF11 0 FF20 1 FF31 1 FF4