4 Commissioning4.5 Acyclic data72 DX-NET-SWD... 08/14 MN04012009Z-EN www.eaton.com4.5.3.1 PNU927Parameter 927 can be used to switch between parameter levels; theparameter can be set to a value of 0 or 1:• 0: Parameters can be changed directly on the variable frequency drive/variable speed starter and not via SmartWire-DT,with the exception of parameters 927 and 928.• 1: Parameters can be changed via SmartWire-DT and not directly on thevariable frequency drive/variable speed starter,with the exception of parameters 927 and 928.4.5.3.2 PNU928 (ProcessData Access)Parameter PNU 928 has the following options:This parameter does not exist in the basic devices‘ display. It behavessimilarly to parameter P1-12 in DA1 variable frequency drives and parameterP-12 in DC1 variable frequency drives and DE1 variable speed starters:It has an offset of 8, except for the 0 setting.Value Description0 Control signal terminals (I/O)The variable frequency drive will respond directly to signals applied to the control signal terminals.1 Control commands and setpoint via SmartWire-DT: DI1 = Hardware enable, P-15: No function2 Control commands via SmartWire-DT: Local setpoint (P-15 for local settings)3 Local control commands, setpoint values via SmartWire-DT (DI1 = Start / Stop)4 Actuation via SmartWire-DT - depending on the settings with the loss in communication, automaticchange to the local actuation5 Control commands and setpoint via SmartWire-DT. Additionally via DI1 Enable and DI2 EnableSetpointValue Description0 Control signal terminals (I/O)The variable frequency drive will respond directly to signals applied to the control signal terminals.1 specific to the deviceFor more information, please refer to the manual for the corresponding basic device.…89 Control commands and setpoint via SmartWire-DT: DI1 = Hardware enable, PNU 423 has no function10 Control commands via SmartWire-DT: Local setpoint (PNU 423 for local settings)11 Local control commands, setpoint values via SmartWire-DT (DI1 = Start / Stop)12 Actuation via SmartWire-DT - depending on the settings with the loss in communication, automaticchange to the local actuation13 Control commands and setpoint via SmartWire-DT. Additionally via DI1 Enable and DI2 EnableSetpoint