4 Commissioning4.5 Acyclic dataDX-NET-SWD... 08/14 MN04012009Z-EN www.eaton.com 63682 0 – P-51 P-33 RUN rw UInt16 SwitchRemanentStorage If this function is enabled,the computed thermal modelfor the motor will beautomatically saved whenthe supply voltage isswitched off. The storedvalues will then be usedwhen it is switched back on.If the function is disabled,the "thermal memory" will beset to zero every time thesupply voltage is switchedback on.751 0 ✓ – – STOP ro RO1 LogicStatus1 ✓ – – STOP ro RO2 LogicStatus2 ✓ – – STOP ro RO3 LogicStatus3 ✓ – – STOP ro RO4 LogicStatus4 ✓ – – STOP ro RO5 LogicStatus811 0 P0-07 – – STOP ro Interface0 f-Reference Current field bus speedreference value812 1 P0-67 – – STOP ro Interface M-setpoint Current field bus torquesetpoint813 0 P0-59 – – STOP ro f-setpointoffreq-setpoint Frequency input setpoint821 0 P0-31 P00-10 P00-10 STOP ro U32 t-Run The drive's total operatingtime since the date ofmanufacture, in hours,minutes and seconds.1 P0-35 – – STOP ro Fan operating time R Fan operating time – can bereset2 P0-65 – – STOP ro t-HoursPowerON Number of drive power-onhours3 P0-34 P00-13 P00-13 STOP ro U32 t-HoursRunEnable The drive's operating timesince the most recent enablesignal, in hours, minutes, andseconds.4 P0-35 – – STOP ro Fan operating time Total fan operating time25 - 500 P0-32 P00-12 P00-12 STOP ro U32 RunSinceLastTrip The drive's operating timesince the most recent fault,in hours, minutes, andseconds.6 P0-24 – – STOP ro t-Run PCB in OT The drive's operating hoursat a temperature higher than80 °C inside the housing7 P0-23 – – STOP ro t-Run IGBT in OT The drive's operating hoursat a heat sink temperaturehigher than 85 °C8 P0-73 – – STOP ro t-PowerOn The drive's operating time9 P0-22 – – STOP ro TimeToNextService Time to next servicePNUIndexPNUSubindexParameter number inspecific deviceAccess right Data type Name DescriptionDA1 DC1 DE1 RUN/STOPro/rw