4 Commissioning4.4 Cyclic dataDX-NET-SWD... 08/14 MN04012009Z-EN www.eaton.com 391 0 ERR Error present0: no error1: ErrorIndicates whether there is a variable frequency drive/variable speed starterfault. If there is one, the device will respond as configured in PNU 362.0.1 WARN Warning present0: no warning1: WarningIndicates whether there is a variable frequency drive/variable speed starterwarning.2 RDY Ready, switched on0: not switched on1: switched onIndicates whether the variable frequency drive/variable speed starter isswitched on.3 f = f-ref operation at setpoint0: Ref. frequency not reached1: Ref. frequency reachedAs long as the slip compensation is lower than 5%, this parameter willhave a value of 1. The bit's value will change to 0 for values higher than5%.• DC1, DE1: The bit will have a constant value of 1.In the event of a fault, the value will change to 0.• DA1: If the slip frequency is lower than 5%([(P0-63)-(P0-60))/(P0-63] < 5%), the value will be 1. Otherwise, thevalue will be 0.4 f-Level Actual speed is greater than the signalling threshold0: Actual speed is less than or equal to the signaling threshold1: Actual speed is greater than the signalling thresholdIf the actual speed is greater than the value set on relay output 1, the valuewill be 1. Otherwise, it will be 0.• DC1, DE1: P00-03 ≧ P-19• DA1: Depending on the operating mode: P0-60 or P0-25 ≧ P2-165 Q 1 Device Info Q1The bit will have a value of 1 if the condition below is met; otherwise, itwill have a value of 0.• DC1, DE1: The motor current is greater than the limit value –comparable to the relay function if P-18 = 5.• DA1: The motor's torque is greater than the limit value – comparableto the relay function if P2-16 = 6.6 Q2 Device Info Q2Reserved – not used as of this writing7 Q3 Device Info Q3Reserved – not used as of this writingByte: BIT Designation Meaning