S611 Soft Starter MN03902011E—May 2012 www.eaton.com 39Appendix A—ParametersParameter ListsOperation Mode—StandardOperating Parameter Units Minimum Maximum Default NotesMotor FLA Amps Motor FLA parametermust be set to motornameplate FLA toachieve proper overloadprotectionFrame Size A–52 26 52 26Frame Size A–65 32.5 65 32.5Frame Size A–77 38.5 77 38.5Frame Size B–99 48 99 48Frame Size B–125 62.5 125 62.5Frame Size C–156 78 156 78Frame Size C–180 90 180 90Frame Size D–242 120 242 120Frame Size E–302 151 302 151Frame Size E–361 180.5 361 180.5Frame Size F–414 207 414 207Motor rated voltage Volts 200 600 480 —Start method — 0 1 0 0 = Voltage ramp1 = Current limitStart time Seconds 0.5 180 20 —Initial torque % 0 100 45 —Stop time Seconds 0 60 0 —Kick start time Seconds 0 2 0 —Kick start torque % 0 100 0 —Auto reset mode — 0 1 0 0 = Manual1 = AutoAdvanced config — N/A N/A N/A —www.comoso.com