40 S611 Soft Starter MN03902011E—May 2012 www.eaton.comOperation Mode—Pump OptionProtection ModeNote: Setting any parameter to OFF disables the protection.Operating Parameter Units Minimum Maximum Default NotesMotor FLA Amps Motor FLA parametermust be set to motornameplate FLA toachieve proper overloadprotectionFrame Size A–52 26 52 26Frame Size A–65 32.5 65 32.5Frame Size A–77 38.5 77 38.5Frame Size B–99 48 99 48Frame Size B–125 62.5 125 62.5Frame Size C–156 78 156 78Frame Size C–180 90 180 90Frame Size D–242 120 242 120Frame Size E–302 151 302 151Frame Size E–361 180.5 361 180.5Frame Size F–414 207 414 207Motor rated voltage Volts 200 600 480 —Start method — 0 2 2 0 = Voltage ramp1 = Current limit2 = Pump startStart time Seconds 0.5 180 20 —Initial torque % 0 100 45 —Stop time Seconds 0 60 5 —Kick start time Seconds 0 2 0 —Kick start torque % 0 100 0 —Auto reset mode — 0 1 0 0 = Manual1 = AutoAdvanced config — N/A N/A N/A —Protection Parameter Units Minimum Maximum DefaultTrip class — Off, 5 30 20Jam trip % Off, 150 400 300Stall trip % Off, 150 400 200Current imbalance % Off, 1 100 20Under load % Off, 1 50 OffPhase loss % Off, 1 100 40Under voltage % Off, 1 99 90Over voltage % Off, 101 120 110Voltage imbalance % Off, 1 20 6Phase sequence — Off, ABC ACB ABCwww.comoso.com