46 S611 Soft Starter MN03902011E—May 2012 www.eaton.comFault DisplayThe S611 indicates most faults with a fault code and by illuminating the corresponding modeand Protection/Operation (P/O) LEDs. In addition, the dedicated Fault LED will be illuminatedwhen the device is faulted.Fault DisplayFault FCUser InterfaceMode LED P/O LED DisplayWatchdog firmware 3 None None F.03FRam 5 None None F.05User interface com failure 6 None None F.06Flash CRC 7 None None F.07Zero volt cross lost 8 None None F.08Comm lost port A 9 None None F.09Comm lost port B 10 None None F.10Pole over temp 15 None None F.15Bypass dropout 16 None None F.16SCR not firing 17 None None F.17Shorted SCR 18 None None F.18Instantaneous SCR overcurrent 19 None None F.19Motor overload 20 Operation Motor FLA F.20Mains loss 21 Protection Under voltage (V) F.21Under voltage 22 Protection Under voltage (V) F22Over voltage 23 Protection Over voltage (V) F.23Phase reversal 24 Protection Phase sequence F.24Stall 25 Protection Stall trip % F.25SCR overcurrent 27 None None F.27Under load 28 Protection Under load F.28Current imbalance 29 Protection Current imbalance % F.29Phase loss 30 Protection Phase loss % F.30Voltage imbalance 31 Protection Voltage imbalance % F.31Jam 33 Protection Jam trip % F.33Contactor overcurrent 34 None None F.34Missing temp sensor 35 None None F.35www.comoso.com