4-2 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUALENERVISTA SOFTWARE INTERFACE CHAPTER 4: INTERFACES4• Remote resources• TestingFactory default values are supplied and can be restored after any changes.The following communications settings are not transferred to the B30 with settings files:Modbus Slave AddressModbus TCP Port NumberRS485 COM2 Baud RateRS485 COM2 ParityCOM2 Minimum Response TimeCOM2 SelectionRRTD Slave AddressRRTD Baud RateIP AddressIP Subnet MaskIP RoutingWhen a settings file is loaded to a B30 that is in-service, the following sequence occurs:1. The B30 takes itself out of service.2. The B30 issues a UNIT NOT PROGRAMMED major self-test error.3. The B30 closes the critical fail contact.The Maintenance chapter outlines how to use a settings file in the .urs format for backup and restore.4.1.3 Event viewingIn online or offline mode, you can view and analyze data generated by triggered parameters as follows:• Event recorder — The event recorder captures contextual data associated with the last 1024 events, listedchronologically from most recent to oldest• Oscillography — The oscillography waveform traces and digital states are used to provide a visual display of powersystem and relay operation data captured during specific triggered eventsEvent records are viewable at software and device-specific levels. Access the former under Admin > Event Log > View.Access the latter under Actual Values > Records > Event Record.Event record entries for CyberSentry are explained in the next chapter. The following table outlines some software-levelentries.Table 4-1: Event record descriptionsEvent DescriptionEnerVista UR Setup SESSION STARTED The EnerVista software was launchedLanguage was changed. The user changed the software language using the View > Language menu itemDEFAULT USERS CREATED The user management window was launched using the Admin > User Management menuitem: Successful upload of firmwareENDFirmware verifiedFirmware uploadedFirmware erasedSTART: Upload new firmwareThe firmware on a device was upgradedEnerVista UR Setup EVENT LOG CLEARED The event record was cleared. All event records were deleted using the Admin > Event Log >Clear menu item.