CHAPTER 5: SETTINGS PRODUCT SETUPB30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 5-955FltRptRFLO1.RsStat.ctlModelRange: direct-with-normal-security, sbo-with-normal-securityDefault: direct-with-normal-securityThis setting selects the control model clients must use to successfully control the command CLEAR FAULT REPORTS. "sbo"here is select-before-operate. Enhanced security means that the B30 reports to the client the breaker 1 position at theend of the command sequence.LLN0.EvtRcdClr.ctlModelRange: direct-with-normal-security, sbo-with-normal-securityDefault: direct-with-normal-securityThis setting selects the control model clients must use to successfully control the command CLEAR EVENT RECORDS.LPHD1.RsStat.ctlModelRange: direct-with-normal-security, sbo-with-normal-securityDefault: direct-with-normal-securityThis setting selects the control model clients must use to successfully control the command CLEAR ALL RELAY RECORDS.OscRDRE1.RcdTrg.ctlModelRange: direct-with-normal-security, sbo-with-normal-securityDefault: direct-with-normal-securityThis setting selects the control model clients must use to successfully control the command FORCE TRIGGER.OscRDRE1.MemClr.ctlModelRange: direct-with-normal-security, sbo-with-normal-securityDefault: direct-with-normal-securityThis setting selects the control model clients must use to successfully control the command CLEAR OSCILLOGRAPHY.DatLogRDRE1.MemClr.ctlModelRange: direct-with-normal-security, sbo-with-normal-securityDefault: direct-with-normal-securityThis setting selects the control model clients must use to successfully control the command CLEAR DATA LOGGER.CBArc0SCBR1.MemClr.ctlModelRange: direct-with-normal-security, sbo-with-normal-securityDefault: direct-with-normal-securityDmdMtrMMTR1.RsStat.ctlModelRange: direct-with-normal-security, sbo-with-normal-securityDefault: direct-with-normal-securityEnrMtrMMTR1.RsStat.ctlModelRange: direct-with-normal-security, sbo-with-normal-securityDefault: direct-with-normal-securityGGIO1GGIO1 is a UR feature that allows up to 128 UR FlexLogic operands to be user-mapped to IEC 61850 information modeldata attributes.For the value of a FlexLogic operand to be read via MMS, included in TxGOOSE messages, or included in buffered/unbuffered reports, the value must be assigned to a data attribute. GGIO1 allows those FlexLogic operands that have notyet been factory-assigned to a data attribute to be user-assigned to a generic data attribute, and thus have their valuesincluded in IEC 61850 communications.Navigate to Settings > Product Setup > Communications > IEC 61850 > GGIO > GGIO1 to access the settings for GGIO1.