5-184 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUALFLEXLOGIC CHAPTER 5: SETTINGS5A FlexElement is a universal comparator used to monitor any analog actual value calculated by the relay or a netdifference of any two analog actual values of the same type. The effective operating signal can be treated as a signednumber or its absolute value can be used.FlexElements run every half power cycle (every four protection passes).The element can be programmed to respond either to a signal level or to a rate-of-change (delta) over a pre-defined periodof time. The output operand is asserted when the operating signal is higher than a threshold or lower than a threshold, asper your choice. FLEXELEMENT 1 INPUTMODE: SIGNEDRange: SIGNED, ABSOLUTE FLEXELEMENT 1 COMPMODE: LEVELRange: LEVEL, DELTA FLEXELEMENT 1DIRECTION: OVERRange: OVER, UNDER FLEXELEMENT 1PICKUP: 1.000 puRange: –90.000 to 90.000 pu in steps of 0.001 FLEXELEMENT 1HYSTERESIS: 3.0%Range: 0.1 to 50.0% in steps of 0.1 FLEXELEMENT 1 dtUNIT: MillisecondsRange: Milliseconds, Seconds, Minutes FLEXELEMENT 1 dt:20Range: 20 to 86400 in steps of 1 FLEXELEMENT 1 PKPDELAY: 0.000 sRange: 0.000 to 65.535 s in steps of 0.001 FLEXELEMENT 1 RSTDELAY: 0.000 sRange: 0.000 to 65.535 s in steps of 0.001 FLEXELEMENT 1 BLK:OffRange: FlexLogic operand FLEXELEMENT 1TARGET: Self-resetRange: Self-reset, Disabled, Latched FLEXELEMENT 1EVENTS: DisabledRange: Disabled, Enabled