A2 Metering 745Transformer Management RelayActual Valueshttp://www.GEindustrial.com/multilin 6ñ7GE Multilinf) Differential CurrentPATH: ACTUAL VALUES !" A2 METERING ! CURRENT !" DIFFERENTIALThe differential current magnitudes and angles for Phases A, B, and C are shown.The differential current phase angles are referenced to Winding 1 Phase A current.g) Restraint CurrentPATH: ACTUAL VALUES !" A2 METERING ! CURRENT !" RESTRAINTThe restraint current magnitudes for phases A, B, and C are shown here.h) Ground Differential CurrentPATH: ACTUAL VALUES !" A2 METERING ! CURRENT !" GROUND DIFFERENTIALThe ground differential current magnitudes for Windings 1 through 3 are shown.! DIFFERENTIAL [!] PHASE A DIFFERENTIALCURRENT: 0.00 x CTMESSAGE PHASE A DIFFERENTIALANGLE: 0∞ LagMESSAGE PHASE B DIFFERENTIALCURRENT: 0.00 x CTMESSAGE PHASE B DIFFERENTIALANGLE: 0∞ LagMESSAGE PHASE C DIFFERENTIALCURRENT: 0.00 x CTMESSAGE PHASE C DIFFERENTIALANGLE: 0∞ Lag! RESTRAINT [!] PHASE A RESTRAINTCURRENT: 0.00 x CTMESSAGE PHASE B RESTRAINTCURRENT: 0.00 x CTMESSAGE PHASE C RESTRAINTCURRENT: 0.00 x CT! GROUND [!]DIFFERENTIALW1 GND DIFFERENTIALCURRENT: 0.00 x CTMESSAGE W2 GND DIFFERENTIALCURRENT: 0.00 x CTMESSAGE W3 GND DIFFERENTIALCURRENT: 0.00 x CT