GEK-113032A W650 Wind Generator Protection System 7-157 IEC 61850 PROTOCOL 7.2 IEC 61850 PROFILE FOR W6507NDPTOC: 3 NEUTRAL TIME OVERCURRENT.GNDPTOC: 3 GROUND TIME OVERCURRENT AND 3 SENS GROUND TIME OVERCURRENT.PTOC CLASSAttributeNameAttr.TypeExplanation M/O NotesPTOC Time overcurrentDATACommon Logical Node InformationMod geModINC Mode MBeh geINS Behaviour MHealth geINS Health MNamPlt geLPL Name plate MStatus InformationStr geNeutACD Start M TOC PKPOp geNeutACT Operate M TOC OPBlk geNeutACT Block P TOC BLKSettingsTmACrv geCURVE Operating curve type M CurveStrVal geFloatASG Start value O Pickup Level (0,05 - 160)TmMult geFloatASG Time dial multiplier O TD Multiplier (0 – 900)RsMod geING_2 Reset Mode P Reset (instantaneous, lineal)PTOCEna geSPG Function TOC enable P FunctionPTOC CLASSAttributeNameAttr.TypeExplanation M/O NotesPTOC Time overcurrentDATACommon Logical Node InformationMod geModINC Mode MBeh geINS Behaviour MHealth geINS Health MNamPlt geLPL Name plate MStatus InformationStr geNeutACD Start M TOC PKPOp geNeutACT Operate M TOC OPBlk geNeutACT Block P TOC BLKSettingsTmACrv geCURVE Operating curve type M CurveStrVal geFloatASG Start value O Pickup Level (0,05 – 160)TmMult geFloatASG Time dial multiplier O TD Multiplier (0 – 900)RsMod geING_2 Reset Mode P Reset (instantaneous, lineal)InMagTyp geING_1 Input Type P Input (Phasor, RMS)PTOCEna geSPG Function TOC enable P Function