GEK-113032A W650 Wind Generator Protection System E-13APPENDIX E E.1 FACTORY DEFAULT SETTINGSESETPOINT > PROTECTION ELEMENTS > POWER > DIRECTIONAL POWER>DIRECTIONAL POWER 1> DIRECTIONAL POWER 2 > DIRECTIONAL POWER 3 > DIRECTIONAL POWER 4SETTING DESCRIPTION NAME DEFAULT VALUE STEP RANGE USERVALUEFunction permission Function DISABLED N/A [DISABLED – ENABLED]Block from off-line Blk Time After Close 0.00 0.01 s [0.00 : 900.00]Directional Angle for stage 1 Dir Power Angle 1 0.00 1 Deg [0.00 : 359.99]Pickup level for stage 1 Stage 1 Tap 10.00 0.01MW [-10000.00 : 10000.00]Trip time for stage 1 Stage 1 Time 60.00 0.01 s [0.00 : 900.00]Directional Angle for stage 2 Dir Power Angle 2 0.00 1 Deg [0.00 : 359.99]Pickup level for stage 2 Stage 2 Tap 20.00 0.01MW [-10000.00 : 10000.00]Trip time for stage 2 Stage 2 Time 60.00 0.01 s [0.00 : 900.00]Snapshot Event generation Snapshot Events ENABLED N/A [DISABLED – ENABLED]SETPOINT > PROTECTION ELEMENTS > VOLTAGE ELEMENTS >VOLTAGE UNBALANCEVOLTAGE UNBALANCE 1 > VOLTAGE UNBALANCE 2 > VOLTAGE UNBALANCE 3>SETTING DESCRIPTION NAME DEFAULT VALUE STEP RANGE USERVALUEFunction permission Function DISABLED N/A [DISABLED – ENABLED]Pickup Level Pickup Level 1 1 % [3 : 500]Trip Delay Trip Delay 10.00 N/A [DEFINITE TIME –INVERSE TIME]Reset Delay Reset Delay 0.00 [0.00 : 900.00]Snapshot Event generation Snapshot Events ENABLED N/A [DISABLED – ENABLED]SETPOINT > CONTROL ELEMENTS > SETTING GROUPSETTING DESCRIPTION NAME DEFAULT VALUE STEP RANGE USERVALUESetting Grouping Permission Function DISABLED N/A [DISABLED – ENABLED]Active Group Active Group GROUP 1 N/A [GROUP 1 – GROUP 2 –GROUP 3 – GROUP 4]Snapshot Event generation Snapshot Events ENABLED N/A [DISABLED – ENABLED]SETPOINT > CONTROL ELEMENTS > UNDERFREQUENCYUNDERFREQUENCY 1 > UNDERFREQUENCY 2 > UNDERFREQUENCY 3 > UNDERFREQUENCY 4SETTING DESCRIPTION NAME DEFAULT VALUE STEP RANGE USERVALUEFunction permission Function DISABLED N/A [DISABLED – ENABLED]Pickup level Pickup Level 49.50 0.01 Hz [20.00 : 65.00]Trip time Trip Delay 0.00 0.01 s [0.00 : 900.00]Reset time Reset Delay 0.00 0.01 s [0.00 : 900.00]Minimum voltage threshold Minimum Voltage 50 1 V [30 : 500]Snapshot event generation Snapshot Events ENABLED N/A [DISABLED – ENABLED]