D-4 W650 Wind Generator Protection System GEK-113032AD.4 IEC 104 SETTINGS APPENDIX DDD.4IEC 104 SETTINGSThe Communication settings for IEC 60870-5-104 protocol are the following:Function: Enable or disable the protocol operation.TCP Port: Listening TCP port in the relay. Default value is 2404.Common Addr of ASDU: Address in the ASDU header. Default value is 255.Cyclic Meter Period: Number of seconds for instantaneous meterings. 0 means no spontaneousmeterings.Synchronization event: Not implemented.The W650 relay has a custom Binary Inputs points list, called User Map; it is common for any protocol. In the case of IEC104 Protocol, those points are GROUP1 and GROUP2.The IEC 104 User Map can be configured using the EnerVista 650 Setup software in Settings>Relay Configuration->Control Events. The User Map contains 128 Binary Inputs. To each point of the User Map, the user can assign any of thebinary states of the W650 relay, also is possible to combine those states using OR and NOT functions. These states are:contact inputs and outputs, virtual outputs, protection element states, PLC states, etc. The User Map always has a size of128 Binary Inputs. Points in the User Map that are not configured will have a zero value in the answer.It is possible to implement more complex logic than simple OR and NOT using the PLC Editor tool in EnerVista 650 Setupin the menu Settings>Logic Configuration. These complex signals (Virtual Outputs) can be assigned to the binary pointsin the Control Events configuration for the IEC 104 user map.PRODUCT SETUP>COMMUNICATION SETTINGS >IEC 870-5-104NAME VALUE UNITS RANGEFunction DISABLEDTCP Port 2404 [0 : 65535]Common Addr of ASDU 255 [0 : 65535]Cyclic Meter Period 0 [0 : 3600]Synchronization Event 0 [0 : 3600]