GEK-113032A W650 Wind Generator Protection System 2-252 PRODUCT DESCRIPTION 2.4 TECHNICAL SPECIFICATIONS22.4.12 ENVIRONMENTAL CHARACTERISTICS2.4.13 PACKAGING AND WEIGHT2.4.14 TYPE TESTSType test report available upon request.W650 has been designed to comply with the highest existing requirements. More specifically, UNIPEDE recommendationsfor high voltage substations are followed, even if for most applications such high classes are not required.The relay complies with ANSI C37.90 standards, and has been designed to comply with international standards.2.4.15 APPROVALSOperating temperature: - 10°C to + 60°CStorage temperature: - 40°C to + 80°CHumidity (non condensing): 95%Altitude Up to 2000 mInstallation category IINet weight: 5 kgPackaged: 6 kgPackage dimensions: 30x40x40 cm (DxWxH)CATEGORY STANDARD CLASS TESTEMC IEC 61000-4-1 IEC 60255-22-1 III Oscillatory waves immunityIEC 61000-4-2 IEC 60255-22-2 IV Electrostatic discharge immunity testIEC 61000-4-3 IEC 60255-22-3 III Radiated electromagnetic field disturbance testIEC 61000-4-4 IEC 60255-22-4 IV Electrical fast transientIEC 61000-4-5 IEC 60255-22-5 IV Surge immunity testIEC 61000-4-6 IEC 60255-22-6 III Conducted electromagnetic field disturbance testIEC 61000-4-8 EN 61000-4-8 IV Power frequency magnetic field immunityENV50204 III Radiated electromagnetic field disturbance test –1890 MHz.EMC Emisivity IEC 60255-25 EN 61000-6-4 A Conducted and radiated emissionsProduct IEC 60255-5 2 kV Insulation resistance – dielectric testIEC 60255-5 6kV .5J Impulse testIEC 60255-11 100 ms Power supply Voltage dips/interruptions/variations:Mechanical IEC 60255-21-1 I Vibration test (sinusoidal)IEC 60255-21-2IEC 60255-21-3IIIShock and bumpSeismicISO9001 Registered system.CE marking: Meets the CE standards relevant for protections.