GEK-113032A W650 Wind Generator Protection System D-5APPENDIX D D.5 IEC 60870-5-104 POINT LISTDD.5IEC 60870-5-104 POINT LISTa) SELECTION OF STANDARD ASDUS:Process information in monitor direction<1> Single-point information M_SP_NA_1<2> Double-point information M_DP_NA_1<3> Measured value, short floating point value M_ME_NC_1Process information in control direction<46> Single command C_SC_NA_1System information in control direction<106> Reset process command C_RP_NA_1The W650 relay has a custom Binary Inputs points list, called User Map; it is common for any protocol. In the case of IEC104 Protocol, those points are GROUP1 and GROUP2.GROUP 1 STATUSPOINT DESCRIPTIONM_ SP_NA_1 Points1000-1063 CONTROL EVENTSGROUP 2 STATUSPOINT DESCRIPTIONM_ SP_NA_1 Points1064-1127 CONTROL EVENTSGROUP 3 STATUSPOINT DESCRIPTIONM_ DP_NA_1 Points1500-1515 SWITCHGEAR EVENTS