GEK-113032A W650 Wind Generator Protection System B-71APPENDIX B B.7 MEMORY MAPBADDRESS BIT NAME FORMAT STEP MODE LENGTH MISCELLANEOUSAjustes Sobreintensidad Temporizada de Neutro Grupo 3 - Neutral TOC 3 (cont.)0x244C Confirmation address W 1Ajustes Sobreintensidad Temporizada de Tierra Grupo 1 - Ground TOC 10x244D Function F012 1 R/W 1 0=DISABLED1=ENABLED0x244E Input F012 1 R/W 1 0=PHASOR(DFT)1=RMS0x244F Pickup Level F003 1 R/W 2 [0.05 , 160.00] A0x2451 Curve F012 1 R/W 1 0=IEEE Ext Inv1=IEEE Very Inv2=IEEE Mod Inv3=IEC Curve A4=IEC Curve B5=IEC Curve C6=IEC Long-Time Inv7=IEC Short-Time Inv8=IAC Ext Inv9=IAC Very Inv10=IAC Mod Inv11=ANSI Ext Inv12=ANSI Very Inv13=ANSI Norm Inv14=ANSI Mod Inv15=I2t16=Definite Time17=Rectifier Curve18=User Curve A19=User Curve B20=User Curve C21=User Curve D0x2452 TD Multiplier F003 1 R/W 2 [0.00 , 900.00] s0x2454 Reset F012 1 R/W 1 0=INSTANTANEOUS1=LINEAL0x2455 Snapshot Events F012 1 R/W 1 0=DISABLED1=ENABLED0x2468 Confirmation address W 1Ajustes Sobreintensidad Temporizada de Tierra Grupo 2 - Ground TOC 20x2469 Function F012 1 R/W 1 0=DISABLED1=ENABLED0x246A Input F012 1 R/W 1 0=PHASOR(DFT)1=RMS0x246B Pickup Level F003 1 R/W 2 [0.05 , 160.00] A0x246D Curve F012 1 R/W 1 0=IEEE Ext Inv1=IEEE Very Inv2=IEEE Mod Inv3=IEC Curve A4=IEC Curve B5=IEC Curve C6=IEC Long-Time Inv7=IEC Short-Time Inv8=IAC Ext Inv