E-10 W650 Wind Generator Protection System GEK-113032AE.1 FACTORY DEFAULT SETTINGS APPENDIX EESETPOINT > PROTECTION ELEMENTS > GROUND CURRENT > GROUND IOCGROUND IOC 1> GROUND IOC 2 > GROUND IOC 3SETTING DESCRIPTION NAME DEFAULT VALUE STEP RANGE USERVALUEFunction permission Function DISABLED N/A [DISABLED – ENABLED]Input type Input PHASOR(DFT) N/A [PHASOR – RMS]Pickup level Pickup Level 30.00 0.01 A [0.05 : 160.00]Trip time Trip Delay 0.00 0.01 s [0.00 : 900.00]Reset time Reset Delay 0.00 0.01 s [0.00 : 900.00]Snapshot event generation Snapshot Events ENABLED N/A [DISABLED – ENABLED]SETPOINT > PROTECTION ELEMENTS > GROUND CURRENT > GROUND DIRECTIONAL >GROUND DIRECTIONAL 1> GROUND DIRECTIONAL 2 > GROUND DIRECTIONAL 3SETTING DESCRIPTION NAME DEFAULT VALUE STEP RANGE USERVALUEFunction permission Function DISABLED N/A [DISABLED – ENABLED]Maximum Torque Angle MTA -45 1 Deg [-90 : +90]Operation Direction Direction FORWARD N/A [FORWARD – REVERSE]Polarization type Polarization VO N/A [V 0 – IP – V 0 +I P – V 0 *IP ]Block logic type Block Logic PERMISSION N/A [BLOCK – PERMISSION]Polarization voltage threshold Pol V Threshold 10 1 V [0 : 500]Snapshot event generation Snapshot Events ENABLED N/A [DISABLED – ENABLED]SETPOINT > PROTECTION ELEMENTS > SENSITIVE GROUND CURRENT > SENSITIVE GROUND TOCSENSITIVE GROUND TOC 1> SENSITIVE GROUND TOC 2 > SENSITIVE GROUND TOC 3SETTING DESCRIPTION NAME DEFAULT VALUE STEP RANGE USERVALUEFunction permission Function DISABLED N/A [DISABLED – ENABLED]Input type Input PHASOR(DFT) N/A [PHASOR – RMS]Pickup level Pickup Level 0.050 0.001 A [0.005 : 16.000]Curve shape Curve IEEE Ext Inv N/A [See list of curves]Time Dial TD Multiplier 1.00 0.01 s [0.00 : 900.00]Reset type Reset INSTANTANEOUS N/A [INSTANTANEOUS –LINEAR]Snapshot Event generation Snapshot Events ENABLED N/A [DISABLED – ENABLED]