GEK-113032A W650 Wind Generator Protection System 2-232 PRODUCT DESCRIPTION 2.4 TECHNICAL SPECIFICATIONS2Default Baud Rate 19200Protocols available: ModBus ® RTU / DNP 3.0Typical distance: 1200 mIsolation: dc kV1CAN PORT:Rear port: Fiber CAN port in models X, Y, Z and cable CAN port in models C and M forrear board 1Physical Layer: ISO11898, High speedBaud rate: 125 / 500 kbaudFiber Type: Multimode glass F.O. port with ST connectorsFiber Wave length: 1300 nmFiber type: multimode 62.5/125 μm or 50/125 μmMaximum recommended length 1km (fiber); 500m (cable)Isolation: 2 kVETHERNET PORT:Rear port: COM3Type (depending on model):Model B: 10/100BaseTX self-negotiableModel C: 10/100BaseTX + 100Base FXModel D: 10/100BaseTX + redundant 100BaseFX (Physical media redundancy)Model E: Redundant 10/100BaseTX self-negotiable ports10/100BaseTX RJ45 connector100BaseFX ST connectorsWave length: 1300 nmFiber type: multimode 62.5/125 μm or 50/125 μmProtocols available: ModBus® TCP/IPDNP over TCP/IP and UDP/IPIEC 61850Http, ftp, tftp (allow the use of a standard Internet browser)Typical distance: 1.65 kmResponse time to ModBus commands: 10 ms TypicalIsolation: 2 kVIn Models C and D, the 10/100BaseTX port is selected by an internal switch (see 3.3.3)Two witness LED’s for transmission and reception are included