Multi I/O Unit Setting5-65.2.2 Allocation of Contacts to Output TerminalsThe contact allocation function to output terminals is a function to allocate Y contacts to outputterminals by four points. The arrangement can be changed from the initial state and the sameY contact can be allocated to multiple terminals. Example of contact allocationIn this example, "Output terminal polarity" is set to use sink and source outputs and thesignals of A15-A18 are replaced with the signals of B11-B14.In this example, "Output terminal polarity" is set to use two kinds of push-pull outputs and thesame Y contact is allocated to two output circuits.(Note): When the polarities are mixed, a warning occurs and the ERR LED on the unit flashes for urging users tocheck the wiring. To make warnings not to be announced, set "Warning annunciation" to "Not announce" in the"Multi I/O Unit Setting" screen of FPWIN GR7 (Ver.1.1 or later), or set the bit 9 of UM00062 to 1.