Counter Function7-47.1.2 Configuration Using Tool SoftwareThe setting of the counter function is specified in the configuration menu of FPWIN GR7. Setting methodThe following procedure shows the case that "High-speed counter (Phase input)" is allocatedto the inputs (X100-103) of the multi I/O unit registered in the starting word number 10. It alsodescribes the procedure when the multi I/O unit has been already allocated in the I/O map.PROCEDURE1. Select "Options" > "Multi I/O Unit Setting" in the menu bar.The "Mufti I/O Unit Setting" dialog box will be displayed. Select a unit to be used.2. Select "High-speed counter" from the "Selection of function" tree, anddouble-click an input number to which the high-speed counter is allocated.The "High-speed counter Advanced" dialog box is displayed.3. Select "Phase input (4 multiple)" from the "Function setting" drop-down list.4. Input a preset value or upper and lower limit values as necessary.5. Press the [OK] button.The selected condition will be registered on the "Multi I/O Unit Setting" dialog box.