Interrupt Function6-86.2.2 Comparison Match Interrupt Overview• The high-speed counters are allocated to the inputs (X100-X103) of the multi I/O unit.(For the interrupt occurred when comparison values match)• The interrupt (INT0) occurs when the counted pulse number agrees with the "comparisonoutput setting value" that has been specified. The interrupt program from INT0 of asequence program until IRET is executed, and the output (Y160) of the 32-point output unitis output at a high speed.(For the interrupt occurred at the same time as comparison output)• The interrupt (INT0) occurs at the same time as the comparison output. The interruptprogram from INT0 of a sequence program until IRET is executed, and the output (Y160) ofthe 32-point output unit is output at a high speed.X100X1010 V (24 V DC)X103(CH0 MASK)(CH0 IN-A)(CH0 IN-B)Y160X102(CH0 RST)X140WX10-WX13WY10-WY13 WX14WX15 WY16WY17Multi I/O unit32-point input unit32-point output unit