u Three-Phase 200 V Class Drive Models 2A0040 to 2A0211Table A.2 Power Ratings Continued (Three-Phase 200 V Class)Item SpecificationDrive Model 2A0040 2A0056 2A0069 2A0081 2A0110 2A0138 2A0169 2A0211Maximum ApplicableMotor Capacity (HP) <1> ND Rating 15 20 25 30 40 50 60 75InputInput Current (A) <2> ND Rating 52 68 80 96 111 136 164 200Rated VoltageRated Frequency Three-phase 200 to 240 Vac 50/60 Hz/270 to 340 Vdc <3>Allowable Voltage Fluctuation -15 to 10%Allowable Frequency Fluctuation ±5%Input Power (kVA) ND Rating 27 36 44 52 51 62 75 91OutputRated Output Capacity(kVA) <4> ND Rating <5> 15.2 21 26 31 42 53 64 80Rated Output Current (A) ND Rating <5> 40 56 69 81 110 138 169 211Overload Tolerance ND Rating: 120% of rated output current for 60 s(Derating may be required for applications that start and stop frequently)Carrier Frequency User-adjustable between 1 and 15 kHz <5>User-adjustablebetween 1 and10 kHz <5>Maximum Output Voltage (V) Three-phase 200 to 240 V (proportional to input voltage)Maximum Output Frequency (Hz) 400 Hz (user-set)<1> The motor capacity (HP) refers to a NEC rated 4-pole motor. The rated output current of the drive output amps should be equal to or greater thanthe motor current. Select the appropriate capacity drive if operating the motor continuously above motor nameplate current.<2> Assumes operation at the rated output current. Input current rating varies depending on the power supply transformer, input reactor, wiringconnections, and power supply impedance.<3> DC is not available for UL/CE standards.<4> Rated motor capacity is calculated with a rated output voltage of 220 V.<5> Carrier frequency default setting is Swing PWM 1 (C6-02 = 7). C6-02 settings 1, 7, 8, 9, and A do not require current derating. All other settingsraise the carrier frequency and require current derating.A.1 Power RatingsYASKAWA ELECTRIC TOEP YAIP1U 01B YASKAWA AC Drive - P1000 Quick Start Guide 171A Specifications