No.(Addr.Hex) Name Description Values Pageo4-03(50E) Cooling Fan Operation TimeSettingSets the value of the fan operation time monitor U4-03 in units of 10 h. Default: 0Min.: 0Max.: 9999 –o4-05(51D) Capacitor MaintenanceSettingSets the value of the Maintenance Monitor for the capacitors. See U4-05 tocheck when the capacitors may need to be replaced. Default: 0%Min.: 0Max.: 150 –o4-07(523) DC Bus Pre-Charge RelayMaintenance SettingSets the value of the Maintenance Monitor for the soft charge bypass relay.See U4-06 to check when the bypass relay may need to be replaced. Default: 0%Min.: 0Max.: 150 –o4-09(525) IGBT Maintenance Setting Sets the value of the Maintenance Monitor for the IGBTs. See U4-07 for IGBTreplacement times. Default: 0%Min.: 0Max.: 150 –o4-11(510) U2, U3 Initialization0: U2-oo and U3-oo monitor data is not reset when the drive is initialized(A1-03).1: U2-oo and U3-oo monitor data is reset when the drive is initialized(A1-03).Default: 0Range: 0, 1 –o4-12(512) kWh Monitor Initialization 0: U4-10 and U4-11 monitor data is not reset when the drive is initialized(A1-03).1: U4-10 and U4-11 monitor data is reset when the drive is initialized (A1-03).Default: 0Range: 0, 1 –o4-13(528) Number of Run CommandsCounter Initialization0: Number of Run commands counter is not reset when the drive is initialized(A1-03).1: Number of Run commands counter is reset when the drive is initialized(A1-03).Default: 0Range: 0, 1 –o4-17(3100) Set/Reset Real-Time ClockSets the current date and time for the Real-Time Clock.0: - -1: Set2: ResetDefault: 0Range: 0 to 2 84o4-20(81F) Time Display Format Sets the time display format.0: 12-hour1: 24-hourDefault: 0Range: 0, 1 –B.9 o: Operator-Related Settings220 YASKAWA ELECTRIC TOEP YAIP1U 01B YASKAWA AC Drive - P1000 Quick Start Guide