B.1 A: Initialization ParametersTable B.1 Icons Used in Parameter DescriptionsIcon DescriptionParameter can be changed during run.The A parameter group creates the operating environment for the drive. This includes the parameter Access Level, MotorControl Method, Password, User Parameters and more.u A1: InitializationNo.(Addr.Hex) Name Description Values PageA1-00(100)<1>Language Selection0: English1: Japanese2: German3: French4: Italian5: Spanish6: Portuguese7: ChineseDefault: 0Range: 0 to 7 –A1-01(101)<2>Access Level Selection0: View and set A1-01 and A1-04. Uo-oo parameters can also be viewed.1: User Parameters (access to a set of parameters selected by the user, A2-01to A2-32)2: Advanced Access (access to view and set all parameters)Default: 2Range: 0 to 2 –A1-03(103) Initialize Parameters0: No initialization1110: User Initialize (parameter values must be stored using parameter o2-03)2220: 2-Wire initialization3330: 3-Wire initialization5550: oPE04 error reset8008: Pump8009: Pump w/ PI8010: Fan8011: Fan w/ PIDefault: 0Range: 0 to 5550;8008 to 8011 91A1-04(104) Password When the value set into A1-04 does not match the value set into A1-05,parameters A1-01 through A1-03 and A2-01 through A2-33 cannot bechanged.Default: 0000Min.: 0000Max.: 9999 –A1-05(105) Password Setting When the value set into A1-04 does not match the value set into A1-05,parameters A1-01 through A1-03 and A2-01 through A2-33 cannot bechanged.Default: 0000Min.: 0000Max.: 9999 –A1-06(127) Application Preset0: General-purpose8: Pump9: Pump w/PI10: Fan11: Fan w/PINote: This parameter is not settable. It is used as a monitor only.Default: 0Range: 0; 8 to 11 –<1> Parameter setting value is not reset to the default value when the drive is initialized.<2> Default setting value is dependent on the Initialization parameter A1-03.u A2: User ParametersNo.(Addr.Hex) Name Description Values PageA2-01 toA2-32(106 to125)User Parameters 1 to 32Recently edited parameters are listed here. The user can also select parametersto appear here for quicker access. Default: <1>Range: b1-01 toS6-07–A2-33(126) User Parameter AutomaticSelection0: Parameters A2-01 to A2-32 are reserved for the user to create a list of UserParameters.1: Save history of recently viewed parameters. Recently edited parameters willbe saved to A2-17 through A2-32 for quicker access.Default: 0Range: 0, 1 –<1> Default setting value is dependent on the Initialization parameter A1-03.B.1 A: Initialization Parameters184 YASKAWA ELECTRIC TOEP YAIP1U 01B YASKAWA AC Drive - P1000 Quick Start Guide