u Three-Phase 200 V Class Drive Models 2A0250 to 2A0415Table A.3 Power Ratings Continued (Three-Phase 200 V Class)Item SpecificationDrive Models 2A0250 2A0312 2A0360 2A0415Maximum Applicable Motor Capacity (HP) <1> ND Rating 100 125 150 175InputInput Current (A) <2> ND Rating 271 324 394 471Rated VoltageRated Frequency Three-phase 200 to 240 Vac 50/60 Hz/270 to 340 Vdc <3>Allowable Voltage Fluctuation -15 to 10%Allowable Frequency Fluctuation ±5%Input Power (kVA) ND Rating 124 148 180 215OutputRated Output Capacity (kVA) <4> ND Rating <5> 95 119 137 158Rated Output Current (A) ND Rating <5> 250 312 360 415Overload Tolerance ND Rating: 120% of rated output current for 60 s(Derating may be required for applications that start and stop frequently)Carrier Frequency User-adjustable between 1 and 10 kHz <5>Maximum Output Voltage (V) Three-phase 200 to 240 V (proportional to input voltage)Maximum Output Frequency (Hz) 400 Hz (user-set)<1> The motor capacity (HP) refers to a NEC rated 4-pole motor. The rated output current of the drive output amps should be equal to or greater thanthe motor current. Select the appropriate capacity drive if operating the motor continuously above motor nameplate current.<2> Assumes operation at the rated output current. Input current rating varies depending on the power supply transformer, input reactor, wiringconnections, and power supply impedance.<3> DC is not available for UL/CE standards.<4> Rated motor capacity is calculated with a rated output voltage of 220 V.<5> Carrier frequency default setting is Swing PWM 1 (C6-02 = 7). C6-02 settings 1, 7, 8, 9, and A do not require current derating. All other settingsraise the carrier frequency and require current derating.A.1 Power Ratings172 YASKAWA ELECTRIC TOEP YAIP1U 01B YASKAWA AC Drive - P1000 Quick Start Guide