B.5 E: Motor Parametersu E1: V/f PatternNo.(Addr.Hex) Name Description Values PageE1-01(300) Input Voltage SettingThis parameter must be set to the power supply voltage.WARNING!Electrical Shock Hazard. Drive input voltage (not motorvoltage) must be set in E1-01 for the protective features of the drive tofunction properly. Failure to do so may result in equipment damageand/or death or personal injury.Default: 230 V <1>Min.: 155Max.: 255 <1>102E1-03(302) V/f Pattern Selection0: 50 Hz, Constant torque 11: 60 Hz, Constant torque 22: 60 Hz, Constant torque 3 (50 Hz base)3: 72 Hz, Constant torque 4 (60 Hz base)4: 50 Hz, Variable torque 15: 50 Hz, Variable torque 26: 60 Hz, Variable torque 17: 60 Hz, Variable torque 28: 50 Hz, High starting torque 19: 50 Hz, High starting torque 2A: 60 Hz, High starting torque 3B: 60 Hz, High starting torque 4C: 90 Hz (60 Hz base)D: 120 Hz (60 Hz base)E: 180 Hz (60 Hz base)F: Custom V/f, E1-04 through E1-13 settings define the V/f patternDefault: F <2>Range: 0 to 9;A to FF103E1-04(303) Maximum OutputFrequencyThese parameters are only applicable when E1-03 is set to F.To set linear V/f characteristics, set the same values for E1-07 and E1-09.In this case, the setting for E1-08 will be disregarded. Ensure that the fourfrequencies are set according to these rules:E1-09 ≤ E1-07 < E1-06 ≤ E1-11 ≤ E1-04Output Voltage (V)Frequency (Hz)E1-05E1-12E1-13E1-08E1-10E1-09 E1-07 E1-06 E1-11 E1-04Default: 60.0 HzMin.: 40.0Max.: 400.0 106E1-05(304) Maximum Voltage Default: 575 V <1>Min.: 0.0Max.: 255.0106E1-06(305) Base Frequency Default: 60.0 HzMin.: 0.0Max.: E1-04 106E1-07(306) Middle Output Frequency Default: 3.0 HzMin.: 0.0Max.: E1-04 106E1-08(307) Middle Output FrequencyVoltageDefault: 15.0 V <1>Min.: 0.0 VMax.: 255.0 V106E1-09(308) Minimum Output Frequency Default: 1.5 HzMin.: 0.0Max.: E1-04106E1-10(309) Minimum Output FrequencyVoltageDefault: 9.0 V <1>Min.: 0.0 VMax.: 255.0 V106E1-11(30A)<4> Middle Output Frequency 2 Default: 0.0 HzMin.: 0.0Max.: E1-04 106E1-12(30B)<4>Middle Output FrequencyVoltage 2Default: 0.0 VMin.: 0.0Max.: 255.0 V <1> 106E1-13(30C) Base Voltage Default: 0.0 V <3>Min.: 0.0Max.: 255.0 V <1>106<1> Values shown are specific to 200 V class drives. Double the value for 400 V class drives. Multiply the value by 2.875 for 600 V class drives.<2> Parameter setting value is not reset to the default value when the drive is initialized.<3> When Auto-Tuning is performed, E1-13 and E1-05 will be set to the same value.<4> Parameter ignored when E1-11 (Motor 1 Mid Output Frequency 2) and E1-12 (Motor 1 Mid Output Frequency Voltage 2) are set to 0.0.B.5 E: Motor Parameters196 YASKAWA ELECTRIC TOEP YAIP1U 01B YASKAWA AC Drive - P1000 Quick Start Guide