No.(Addr.Hex) Name Description Values PageS2-06(320B) Sequence Timer 2 StartTimeSets the start time for timer 2. The value must be set less than or equal to S2-07. Default: 00:00Min.: 00:00Max.: 24:00 <1> –S2-07(320C) Sequence Timer 2 Stop TimeSets the stop time for timer 2. The value must be set greater than or equal toS2-06. Default: 00:00Min.: 00:00Max.: 24:00 <1> –S2-08(320D) Sequence Timer 2 DaySelectionSets the days for which sequence timer 2 is active.0: Timer disabled1: Daily2: Mon - Fri3: Sat - Sun4: Monday5: Tuesday6: Wednesday7: Thursday8: Friday9: Saturday10: SundayDefault: 0Range: 0 to 10 –S2-09(320E) Sequence Timer 2 SelectionSets the action that occurs when sequence timer 2 is active.0: Digital output only1: Run2: Run - PI disableDefault: 0Range: 0 to 2 –S2-10(320F) Sequence Timer 2 ReferenceSourceSelects the frequency reference source used for running the drive whensequence timer 2 is active (only applicable when S2-09 is set to 1 or 2).0: Operator (d1-01)1: Operator (d1-02)2: Operator (d1-03)3: Operator (d1-04)4: Terminals5: Serial communication6: Option card7: Pulse inputDefault: 0Range: 0 to 7 –S2-11(3210) Sequence Timer 3 StartTimeSets the start time for timer 3. The value must be set less than or equal to S2-12. Default: 00:00Min.: 00:00Max.: 24:00 <1> –S2-12(3211) Sequence Timer 3 Stop TimeSets the stop time for timer 3. The value must be set greater than or equal toS2-11. Default: 00:00Min.: 00:00Max.: 24:00 <1> –S2-13(3212) Sequence Timer 3 DaySelectionSets the days for which sequence timer 3 is active.0: Timer disabled1: Daily2: Mon - Fri3: Sat - Sun4: Monday5: Tuesday6: Wednesday7: Thursday8: Friday9: Saturday10: SundayDefault: 0Range: 0 to 10 –S2-14(3213) Sequence Timer 3 SelectionSets the action that occurs when sequence timer 3 is active.0: Digital output only1: Run2: Run - PI disableDefault: 0Range: 0 to 2 –S2-15(3214) Sequence Timer 3 ReferenceSourceSelects the frequency reference source used for running the drive whensequence timer 3 is active (only applicable when S2-14 is set to 1 or 2).0: Operator (d1-01)1: Operator (d1-02)2: Operator (d1-03)3: Operator (d1-04)4: Terminals5: Serial communication6: Option card7: Pulse inputDefault: 0Range: 0 to 7 –S2-16(3215) Sequence Timer 4 StartTimeSets the start time for timer 4. The value must be set less than or equal to S2-17. Default: 00:00Min.: 00:00Max.: 24:00 <1> –B.10 S: Special Application222 YASKAWA ELECTRIC TOEP YAIP1U 01B YASKAWA AC Drive - P1000 Quick Start Guide