2.4 Mounting periphery modulesRequirements for UL compliance use– Use for power supply exclusively SELV/PELV power supplies.– The System SLIO must be installed and operated in a housingaccording to IEC 61010-1 9.3.2 c).There is a locking lever at the top side of the module. For mounting and demounting thislocking lever is to be turned upwards until this engages. For mounting place the moduleto the module installed before and push the module to the mounting rail guided by thestrips at the upper and lower side of the module. The module is fixed to the mounting railby pushing downward the locking lever. The modules may either separately be mountedto the mounting rail or as block. Here is to be considered that each locking lever isopened. The modules are each installed on a mounting rail. The electronic and powersection supply are connected via the backplane bus. Up to 64 modules may be mounted.Please consider here that the sum current of the electronic power supply does notexceed the maximum value of 3A. By means of the power module 007-1AB10 the currentof the electronic power supply may be expanded accordingly.Each periphery module consists of a terminal and an electronic module.1 Terminal module2 Electronic moduleFor the exchange of a electronic module, the electronic module may be pulled forwardafter pressing the unlocking lever at the lower side of the module. For installation plug theelectronic module guided by the strips at the lower side until this engages audible to theterminal module.Terminal and electronicmoduleVIPA System SLIOBasics and mountingMounting periphery modulesHB300 | SM-AIO | | en | 17-0518