3.6.3 Diagnostic dataSo this module does not support diagnostic interrupt functions, the diagnostics data servefor information about this module. On error the corresponding channel LED of the moduleis activated and the error is registered in the diagnostics data.The following errors are listed in the diagnostics data:n Error in project engineering / parameterizationn Measuring range overflown Measuring range underflowDS - Record set for access via CPU, PROFIBUS and PROFINET. The access happensby DS 01h. Additionally the first 4 bytes may be accessed by DS 00h.IX - Index for access via CANopen. The access happens by IX 2F01h. Additionally thefirst 4 bytes may be accessed by IX 2F00h.SX - Subindex for access via EtherCAT with Index 5005h.More can be found in the according manual of your bus coupler.Name Bytes Function Default DS IX SXERR_A 1 Diagnostic 00h 01h 2F01h 02hMODTYP 1 Module information 15h 03hERR_C 1 reserved 00h 04hERR_D 1 Diagnostic 00h 05hCHTYP 1 Channel type 71h 06hNUMBIT 1 Number diagnostic bitsper channel08h 07hNUMCH 1 Number of channelsof a module02h 08hCHERR 1 Channel error 00h 09hCH0ERR 1 Channel-specific errorchannel 000h 0AhCH1ERR 1 Channel-specific errorchannel 100h 0BhCH2ERR…CH7ERR6 reserved 00h 0Ch ... 11hDIAG_US 4 μs ticker 00h 13hVIPA System SLIO Analog Input031-1BB40 - AI 2x12Bit 0(4)...20mA > Diagnostic dataHB300 | SM-AIO | | en | 17-05 73