At CPU, PROFIBUS and PROFINET the input respectively output area is embedded tothe corresponding address area.IX - Index for access via CANopen with s = Subindex, depends on number and type ofanalog modulesSX - Subindex for access via EtherCAT with Index 6000h + EtherCAT-SlotMore can be found in the according manual of your bus coupler.Addr. Name Bytes Function IX SX+0 AI 0 2 Analog value channel 0 6401h/s 01h+2 AI 1 2 Analog value channel 1 6401h/s+1 02h+4 AI 2 2 Analog value channel 2 6401h/s+2 03h+6 AI 3 2 Analog value channel 3 6401h/s+3 04hNo byte of the output area is used by the module.3.26.1 Technical dataOrder no. 031-1LD80Type SM 031Module ID 0410 1544Current consumption/power lossCurrent consumption from backplane bus 55 mAPower loss 1 WTechnical data analog inputsNumber of inputs 4Cable length, shielded 200 mRated load voltage DC 24 VCurrent consumption from load voltage L+ (without load) 30 mAVoltage inputs -Min. input resistance (voltage range) -Input voltage ranges -Operational limit of voltage ranges -Operational limit of voltage ranges with SFU -Basic error limit voltage ranges -Basic error limit voltage ranges with SFU -Destruction limit voltage -Current inputs -Max. input resistance (current range) -In-/Output areaInput areaOutput areaVIPA System SLIO Analog Input031-1LD80 - AI 4x16Bit R/RTD > Technical dataHB300 | SM-AIO | | en | 17-05 291