4.11.1 Technical dataOrder no. 032-1CB40Type SM 032Module ID 050B 25D8Current consumption/power lossCurrent consumption from backplane bus 60 mAPower loss 0.7 WTechnical data analog outputsNumber of outputs 2Cable length, shielded 200 mRated load voltage DC 24 VReverse polarity protection of rated load voltage üCurrent consumption from load voltage L+ (without load) -Voltage output short-circuit protection -Voltage outputs -Min. load resistance (voltage range) -Max. capacitive load (current range) -Max. inductive load (current range) -Output voltage ranges -Operational limit of voltage ranges -Basic error limit voltage ranges -Destruction limit against external applied voltage -Current outputs üMax. in load resistance (current range) 350 ΩMax. inductive load (current range) 10 mHTyp. open circuit voltage current output 12 VOutput current ranges 0 mA ... +20 mA+4 mA ... +20 mAOperational limit of current ranges +/-0.2%Basic error limit current ranges +/-0.1%Destruction limit against external applied voltage max. 12V (30V for 1s)Settling time for ohmic load 0.25 msSettling time for capacitive load -Settling time for inductive load 1.5 msResolution in bit 16Conversion time 400 μs all channelsSubstitute value can be applied noVIPA System SLIO Analog Output032-1CB40 - AO 2x16Bit 0(4)...20mA > Technical dataHB300 | SM-AIO | | en | 17-05 401