Write ProtectThe parameter ‘Write Protect’ is only relevant, if the module is connectedto a head module with an integrated Web server. If the module is parame-terized via the Web server ‘Write Protect’ must be set to "0", otherwisethe changed parameters will not be used!In the module you can combine some measurands to one data package (Frame), whichis transferred in one step.Ä ‘Frame’ on page 310By specifying the ID of the corresponding measurand, via F0V1 ... F0V5 the data areas ofFrame 0 can be defined. Please note that here the user data length of 12 bytes is notexceeded.Ä Chapter 3.27.6 ‘Measurands’ on page 316n Range of values: 0 ... 41n Default:– F0V1: 1 (active energy consumer)– F0V2: 9 (total active power)– F0V3: 13 (total cos j)– F0V4: 0– F0V5: 03.27.6 MeasurandsID Description Data type Unit Min. value Max. value1 Counter: Active energy consumer INT_32 1Wh * 0 4 294 967 2952 Counter: Active energy producer INT_32 1Wh * 0 4 294 967 2953 Counter: Active energy L1 consumer INT_32 1Wh * 0 4 294 967 2954 Counter: Active energy L1 producer INT_32 1Wh * 0 4 294 967 2955 Counter: Active energy L2 consumer INT_32 1Wh * 0 4 294 967 2956 Counter: Active energy L2 producer INT_32 1Wh * 0 4 294 967 2957 Counter: Active energy L3 consumer INT_32 1Wh * 0 4 294 967 2958 Counter: Active energy L3 producer INT_32 1Wh * 0 4 294 967 2959 Total active power INT_32 1mW -3 750 000 3 750 00010 Total reactive power INT_32 1mW -3 750 000 3 750 00011 Total apparent power INT_32 1mW -3 750 000 3 750 00012 Frequency INT_16 0.01Hz 4600 640013 Total Cos phi *) INT_8 0.01 -100 10014 Temperature INT_16 0.01°C -2500 850015 Active power L1 INT_32 1mW -1 250 000 1 250 00016 Reactive power L1 INT_32 1mW -1 250 000 1 250 00017 Total power L1 INT_32 1mW -1 250 000 1 250 000F0V1 ... F0V5VIPA System SLIOAnalog Input031-1PA00 - AI1x 3Ph 230/400V 1A > MeasurandsHB300 | SM-AIO | | en | 17-05316