IX - Index for access via CANopen with s = Subindex, depends on number and type ofanalog modulesSX - Subindex for access via EtherCAT with Index 6000h + EtherCAT-SlotMore can be found in the according manual of your bus coupler.Addr. Name Bytes Function IX SX+0 AI 0 2 Analog value channel 0 6401h/s 01h+2 AI 1 2 Analog value channel 1 6401h/s+1 02hNo byte of the output area is used by the module.3.9.1 Technical dataOrder no. 031-1BB90Type SM 031Module ID 0403 1543Current consumption/power lossCurrent consumption from backplane bus 85 mAPower loss 1.1 WTechnical data analog inputsNumber of inputs 2Cable length, shielded 200 mRated load voltage DC 24 VCurrent consumption from load voltage L+ (without load) 30 mAVoltage inputs -Min. input resistance (voltage range) 10 MΩInput voltage ranges -80 mV ... +80 mVOperational limit of voltage ranges ±0.3%Operational limit of voltage ranges with SFU ±0.1%Basic error limit voltage ranges ±0.25%Basic error limit voltage ranges with SFU ±0.05%Destruction limit voltage max. 20VCurrent inputs -Max. input resistance (current range) -Input current ranges -Operational limit of current ranges -Operational limit of current ranges with SFU -Basic error limit current ranges -Input areaOutput areaVIPA System SLIOAnalog Input031-1BB90 - AI 2x16Bit TC > Technical dataHB300 | SM-AIO | | en | 17-0596