3.24.2 Parameter dataDS - Record set for access via CPU, PROFIBUS and PROFINETIX - Index for access via CANopenSX - Subindex for access via EtherCAT with Index 3100h + EtherCAT-SlotMore can be found in the according manual of your bus coupler.Name Bytes Function Default DS IX SXDIAG_EN 1 Diagnostics* 00h 00h 3100h 01hRES1 1 reserved* 00h 00h 3101h 02hLIMIT_EN 1 Limit value monitoring* 00h 00h 3102h 03hSUPR 1 Interference frequency suppression 00h 01h 3103h 04hCH0FN 1 Function number channel 0 12h 80h 3104h 05hRES7 1 reserved 00h 80h 3105h 06hCH0UL 2 Upper limit value channel 0 7FFFh 80h 3106h...3107h07hCH0LL 2 Lower limit value channel 0 8000h 80h 3108h...3109h08hCH1FN 1 Function number channel 1 12h 81h 310Ah 09hRES13 1 reserved 00h 81h 310Bh 0AhCH1UL 2 Upper limit value channel 1 7FFFh 81h 310Ch...310Dh0BhCH1LL 2 Lower limit value channel 1 8000h 81h 310Eh...310Fh0ChCH2FN 1 Function number channel 2 12h 82h 3110h 0DhRES19 1 reserved 00h 82h 3111h 0EhCH2UL 2 Upper limit value channel 2 7FFFh 82h 3112h...3113h0FhCH2LL 2 Lower limit value channel 2 8000h 82h 3114h...3115h10hCH3FN 1 Function number channel 3 12h 83h 3116h 11hRES25 1 reserved 00h 83h 3117h 12hCH3UL 2 Upper limit value channel 3 7FFFh 83h 3118h...3119h13hCH3LL 2 Lower limit value channel 3 8000h 83h 311Ah...311Bh14h* This record set may only be transferred at STOP state.Byte Bit 7 ... 00 n Diagnostic interrupt– 00h: disabled– 40h: enabledDIAG_EN Diagnostic inter-ruptVIPA System SLIOAnalog Input031-1CD70 - AI 4x16Bit ±10V > Parameter dataHB300 | SM-AIO | | en | 17-05270