3.6.2 Parameter dataDS - Record set for access via CPU, PROFIBUS and PROFINETIX - Index for access via CANopenSX - Subindex for access via EtherCAT with Index 3100h + EtherCAT-SlotMore can be found in the according manual of your bus coupler.Name Bytes Function Default DS IX SXCH0FN 1 Function number channel 0 31h 80h 3100h 01hCH1FN 1 Function number channel 1 31h 81h 3101h 02hIn the following there are the measuring ranges with corresponding function numberlisted, which were supported by the analog module. With FFh the corresponding channelis deactivated. The formulas listed here allow you to transform an evaluated measuringvalue (digital value) to a value assigned to the measuring range (analog value) and viceversa.Meas. range(funct. no.)Current(I)Decimal(D)Hex Range Formulas0 ... 20mASiemensS7 format(31h)23.52mA 32511 7EFFh overrange20mA 27648 6C00h nominal range10mA 13824 3600h0mA 0 0000h-3.52mA -4864 ED00h underrange0 ... 20mASiemensS5 format(41h)25.00mA 20480 5000h overrange20mA 16384 4000h nominal range10mA 8192 2000h0mA 0 0000h-4,00mA -3277 F333h underrange4 ... 20mASiemensS7 format(30h)22.81mA 32511 7EFFh overrange20mA 27648 6C00h nominal range12mA 13824 3600h4mA 0 0000h1.19mA -4864 ED00h underrange4 ... 20mASiemensS5 format(40h)24.00mA 20480 5000h overrange20mA 16384 4000h nominal range12mA 8192 2000h4mA 0 0000h0.8mA -3277 F333h underrangeCHxFN Function numberchannel x0(4) ... 20mAVIPA System SLIOAnalog Input031-1BB40 - AI 2x12Bit 0(4)...20mA > Parameter dataHB300 | SM-AIO | | en | 17-0572