Output range(funct. no.)Current(I)Decimal(D)Hex Range Formulas0 ... 20mASiemensS7 format(31h)23.52mA 32511 7EFFh overrange20mA 27648 6C00h nominal range10mA 13824 3600h0mA 0 0000hNot possible, is limited to 0mA. underrange0 ... 20mASiemensS5 format(41h)25.00mA 20480 5000h overrange20mA 16384 4000h nominal range10mA 8192 2000h0mA 0 0000hNot possible, is limited to 0mA. underrangeOutput range(funct. no.)Current(I)Decimal(D)Hex Range Formulas4 ... 20mASiemensS7 format(30h)22.81mA 32511 7EFFh overrange20mA 27648 6C00h nominal range12mA 13824 3600h4mA 0 0000h0mA -6912 E500h underrange4 ... 20mASiemensS5 format(40h)24.00mA 20480 5000h overrange20mA 16384 4000h nominal range12mA 8192 2000h4mA 0 0000h0mA -4096 F000h underrange4.5.3 Diagnostic dataSo this module does not support diagnostic interrupt functions, the diagnostics data servefor information about this module. On error the corresponding channel LED of the moduleis activated and the error is registered in the diagnostics data.The following errors are listed in the diagnostics data:n Error in project engineering / parameterizationn Wire-break (if parameterized)0 ... 20mA4 ... 20mAVIPA System SLIO Analog Output032-1BB40 - AO 2x12Bit 0(4)...20mA > Diagnostic dataHB300 | SM-AIO | | en | 17-05 353