3.24.1 Technical dataOrder no. 031-1CD70Type SM 031Module ID 040E 1544Current consumption/power lossCurrent consumption from backplane bus 65 mAPower loss 0.9 WTechnical data analog inputsNumber of inputs 4Cable length, shielded 200 mRated load voltage DC 24 VCurrent consumption from load voltage L+ (without load) 25 mAVoltage inputs üMin. input resistance (voltage range) 200 kΩInput voltage ranges -10 V ... +10 V0 V ... +10 VOperational limit of voltage ranges +/-0.2%Operational limit of voltage ranges with SFU -Basic error limit voltage ranges +/-0.1%Basic error limit voltage ranges with SFU -Destruction limit voltage max. 30VCurrent inputs -Max. input resistance (current range) -Input current ranges -Operational limit of current ranges -Operational limit of current ranges with SFU -Basic error limit current ranges -Radical error limit current ranges with SFU -Destruction limit current inputs (voltage) -Destruction limit current inputs (electrical current) -Resistance inputs -Resistance ranges -Operational limit of resistor ranges -Operational limit of resistor ranges with SFU -Basic error limit -Basic error limit with SFU -Destruction limit resistance inputs -VIPA System SLIO Analog Input031-1CD70 - AI 4x16Bit ±10V > Technical dataHB300 | SM-AIO | | en | 17-05 267