Name Bytes Function Default DS IX SXSUPR 1 Interference frequency suppression 00h 01h 3100h 01hCH0FN 1 Function number channel 0 10h 80h 3101h 02hCH1FN 1 Function number channel 1 10h 81h 3102h 03hCH2FN 1 Function number channel 2 10h 82h 3103h 04hCH3FN 1 Function number channel 3 10h 83h 3104h 05hByte Bit 7 ... 00 n Bit 1, 0: Interference frequency suppression channel 0n Bit 3, 2: Interference frequency suppression channel 1n Bit 5, 4: Interference frequency suppression channel 2n Bit 7, 6: Interference frequency suppression channel 3– 00: deactivated– 01: 60Hz– 10: 50Hze.g.: 10101010: all channels frequency suppression 50HzIn the following there are the measuring ranges with corresponding function numberlisted, which were supported by the analog module. With FFh the corresponding channelis deactivated. The formulas listed here allow you to transform an evaluated measuringvalue (digital value) to a value assigned to the measuring range (analog value) and viceversa.Meas. range(funct. no.)Voltage(U)Decimal(D)Hex Range Formulas0 ... 10VSiemens S7 format(10h)11.76V 32511 7EFFh overrange10V 27648 6C00h nominal range5V 13824 3600h0V 0 0000h-1.76V -4864 ED00h underrange0 ... 10VSiemens S5 format(20h)12.5V 20480 5000h overrange10V 16384 4000h nominal range5V 8192 2000h0V 0 0000h-2V -3277 F333h underrange3.21.3 Diagnostic dataSo this module does not support diagnostic interrupt functions, the diagnostics data servefor information about this module. On error the corresponding channel LED of the moduleis activated and the error is registered in the diagnostics data.SUPR Interference fre-quency suppressionCHxFN Function numberchannel x0 ... 10VVIPA System SLIOAnalog Input031-1CD35 - AI 4x16Bit 0...10V > Diagnostic dataHB300 | SM-AIO | | en | 17-05240