1.10 o: Operator-Related SettingsThese parameters control the various functions, features, and display of the HOA keypad.u o1: HOA Keypad Display SelectionThese parameters determine the data display on the HOA keypad.n o1-01: Drive Mode Unit Monitor SelectionWhen o1-02 is set to 5, any U monitors can be displayed. This parameter will select the monitors. Pressing the up arrow keywill display the following data: frequency reference → rotational direction → output frequency → output current → o1-01selection.Parameter o1-01 selects the content of the last monitor in this sequence. This is done by entering the “1oo” part of“U1-oo”. Certain monitors are not available in some control modes. There is no effect like this on an LCD operator.No. Name Setting Range Defaulto1-01 Drive Mode Unit Monitor Selection104 to 914U1-04 (Control Mode) toU9-14 (Power Monitor) <1>106 (U1-06)<1> U2-oo and U3-oo parameters cannot be selected.n o1-02: User Monitor Selection after Power UpSelects which monitor parameter is displayed upon power up by entering the 1- oo part of U1-oo. Certain monitors arenot available in some control modes. Refer to U: Monitor Parameters on page 164 for a list of monitors.No. Name Setting Range Defaulto1-02 User Monitor Selection after Power Up 1 to 5 <1><1> Default is 1 when b5-01 is set to 0.Default is 3 when b5-01 is set to 1 or 3.Setting 1: Frequency Reference (U1-01)Setting 2: Motor DirectionSetting 3: Output Frequency (U1-02)Setting 4: Output Current (U1-03)Setting 5: User MonitorThe monitor value selected by o1-01 will be displayed.n o1-03: HOA Keypad Display SelectionSets the units used to display the frequency reference and output frequency. Set o1-03 to 3 for user-set units before settingparameters o1-10 and o1-11.No. Name Setting Range Defaulto1-03 HOA Keypad Display Selection 0 to 3 0Setting 0: 0.01 Hz UnitsSetting 1: 0.01% Units (100% = Max Output Frequency)Setting 2: r/min Units (Calculated by the Max Output Frequency and the Number of Motor Poles)Setting 3: User-set Units (Use o1-10, o1-11)Set the value used for the maximum frequency reference to o1-10. Set the placement of the decimal point in this number too1-11.For example, to have the maximum output frequency displayed as “100.00”, set o1-10 = 1000 and o1-11 = 2 (i.e., 1000 with2 decimal points).Note: 1. Parameter o1-03 allows the programmer to change the units used in the following parameters and monitors:U1-01: frequency referenceU1-02: output frequencyU1-16: output frequency after softstarter (accel/decel ramp generator)d1-01 to d1-17: frequency references1.10 o: Operator-Related SettingsYASKAWA ELECTRIC SIEP C710636 10C Z1000U HVAC MATRIX Drive Programming Manual 1331 Parameter Details